Harmonics,  Switchgear,  Low Voltage,  Technical Article

Understanding and Mitigating Harmonics in Electrical Systems

Understanding and Mitigating Harmonics in Electrical Systems

Introduction

In today's electrical installations, the quality of power is more critical than ever. Modern buildings and industrial facilities are filled with sensitive electronic equipment—computers, variable speed drives, electronic ballasts, and uninterruptible power supplies—that are both susceptible to power quality problems and often the cause of them. Poor power quality can lead to overheating neutral conductors, nuisance tripping of circuit breakers, malfunction of sensitive equipment, and costly downtime.

One of the most significant power quality challenges facing engineers and facility managers is harmonics. These distortions in the voltage and current waveforms can cause a range of problems, from overheated transformers to equipment failure. Understanding the sources of harmonics, their effects, and the practical solutions available is essential for designing and maintaining reliable electrical systems.

What Are Harmonics?

In a linear electrical system, the current drawn is a pure sine wave at the fundamental frequency of the power supply (e.g., 50 or 60 Hz). However, modern electronic devices often use "switch-mode power supplies" and other non-linear components that draw current in pulses rather than smooth waves.

These pulse currents can be mathematically modelled as a sum of multiple sinewaves with frequencies that are multiples of the fundamental frequency—these multiples are called harmonics. For example, on a 60 Hz system, the 3rd harmonic is 180 Hz, the 5th is 300 Hz, and so on.

In three-phase systems, the even harmonics (2nd, 4th, etc.) tend to cancel out, leaving odd harmonics as the primary concern. However, the triplen harmonics (3rd, 9th, 15th, etc.) present a particular problem because they do not cancel in the neutral conductor.

The Harmonics Problem: Effects on Electrical Systems

Neutral Overload

One of the most serious practical consequences of harmonics is overload on neutral conductors. In a three-phase system with balanced linear loads, the fundamental (60 Hz) currents cancel out on the neutral conductor, resulting in a neutral current close to zero.

However, the 3rd harmonic currents from each of the three phases are "exactly in phase" and add together on the neutral conductor. This can result in neutral currents that are up to 173% of the phase currents—potentially causing severe overheating and insulation failure. This problem has become so prevalent that many installations now specify oversized or double-sized neutral conductors.

Transformer and Generator Heating

Harmonic currents create additional heat in transformers and generators. This is caused by:

  • Higher eddy current and stray losses in windings and structural parts
  • Increased RMS current for the same delivered real power (kW)
  • Additional heating that standard transformers may not be sized to handle continuously

Standard transformers may need to be derated significantly when supplying harmonic-rich loads, and in severe cases may fail prematurely, requiring replacement in as little as three to five years.

Equipment Malfunction

Voltage distortion caused by harmonic currents can cause computers, UPS systems, and other sensitive electronics to malfunction, fail, or exhibit erratic behaviour. This is why power quality problems in industrial facilities have been estimated to cost over $12 billion annually.

Effective Solutions for Harmonic Mitigation

Oversized Neutral Conductors

One of the most direct solutions is to increase the size of neutral conductors in three-phase systems. IEC Standard 60364-5-52 provides clear guidance:

  • Harmonics < 15%: The neutral conductor may be smaller than the phase conductors (subject to other conditions being met)
  • Harmonics between 15% and 33%: The neutral conductor must be the same size as the phase conductors
  • Harmonics > 33%: The neutral conductor must be sized to carry the neutral current, which may require a larger conductor than the phase conductors

For multicore cables with harmonics above 33%, both the neutral and phase conductors must be sized to carry 1.45 times the load current.

K-Rated Transformers

K-rated transformers are specifically designed to withstand the additional heating and electrical stress caused by non-linear loads that generate harmonic currents. The "K-factor" is a rating that indicates how well a transformer can handle harmonic-rich loads. Standard K-ratings are 1, 4, 9, 13, and 20.

Key benefits of K-rated transformers:

  • Better tolerance to harmonic loading and reduced overheating risk
  • Less need for aggressive transformer derating in harmonic-rich environments
  • Improved lifecycle reliability for power infrastructure

It's important to note that a K-rated transformer does not reduce harmonics in the system—it simply tolerates them better. K-rated transformers achieve this by increasing the size of the core, increasing the size of the neutral conductor, and using special winding techniques to reduce eddy current and skin effect losses.

Harmonic Mitigating Transformers (HMTs)

Harmonic mitigating transformers are designed to reduce harmonics through cancellation. A delta-zigzag configuration, for example, can eliminate 3rd harmonics from the load, with harmonics from phase A and phase C canceling each other out on the secondary winding. This reduces losses and decreases the current flowing through the transformer.

Line Reactors and Chokes

Adding inductance to a circuit, such as through line reactors or DC chokes, inherently reduces harmonic currents. A transformer with higher impedance acts in a similar way to a line reactor, restricting the current flow and thereby reducing harmonics.

Phase-Shifting Transformers

Using transformers in combinations can create multi-pulse systems—for example, two 6-pulse drives with phase-shifted transformers create a 12-pulse system that cancels many harmonics. Four transformers can create a 24-pulse system, providing even greater harmonic cancellation.

Active and Passive Filters

Where harmonics are severe, dedicated harmonic filters may be required. Passive filters use capacitor-inductor circuits tuned to specific harmonic frequencies. Active filters use power electronics to inject a compensation current that cancels out harmonic currents in real-time, adapting to changing load conditions.

Practical Recommendations for Design and Installation

The most cost-effective approach to power quality is to address it during the initial design phase, where solutions may cost as little as 1% to 2% of construction costs. Key recommendations include:

Wiring Practices:

  • Limit the number of receptacles per circuit (3 to 6 instead of the maximum 13)
  • Use double-size neutrals on three-phase systems serving non-linear loads
  • Use separate branch circuits for sensitive equipment
  • Use separate insulated copper grounding conductors rather than relying on conduit

Grounding:

  • Use full-size or upsized grounding conductors
  • Aim for low resistance to ground (10 ohms or less)

Equipment:

  • Specify K-rated transformers where electronic loads are present
  • Use harmonic-rated panelboards and circuit breakers
  • Use bolt-in circuit breakers for more secure connections

Conclusion

Harmonic distortion is a pervasive and growing challenge in modern electrical installations. The proliferation of non-linear electronic loads—from variable speed drives to LED drivers to EV chargers—means that understanding and mitigating harmonics is essential for ensuring reliable, safe, and efficient operation.

The solutions range from simple design changes like oversized neutrals to specialised equipment like K-rated transformers and harmonic mitigating transformers. By understanding the sources and effects of harmonics, electrical professionals can design systems that not only meet code requirements but also provide reliable, long-term service in the face of increasingly challenging power quality demands.

Disclaimer: This article provides a summary of technical information on power quality and harmonics from various industry publications and manufacturer resources. While efforts have been made to accurately represent the content, please refer to official standards and current publications for complete technical details. Final design, specification, and implementation decisions should be made by qualified professionals in accordance with all applicable regulations and standards.

Related Articles

Single-line diagram of a medium voltage protection scheme with relay and substation connections
Technical Guide,  Calculations,  MV Power,  Switchgear

Protection Criteria for Medium Voltage Networks

ABB’s technical guide covers MV network schemes, switching device selection, current/voltage transformers, short-circuit currents, neutral grounding, and equipment protection.

A technician installing Eaton Bussmann series overcurrent protection devices in a panel
Arc Flash,  Calculations,  Switchgear,  Technical Guide

Overcurrent Protection Handbook: Bussmann Series SPD

An overview of Eaton’s Bussmann series Selecting Protective Devices (SPD) Handbook — a 50-year-old industry reference covering fuseology, fault current calculations, selective coordination, and arc flash.

Join the EBSP Newsletter

Weekly industry news, the latest articles, and engineering updates — straight from practicing electrical engineers. No spam, unsubscribe anytime.